3.7 Behavior in the case of power failure and power restore
SENTRON PAC3200
36 Manual, 02/2008, A5E01168664B-04
3.7 Behavior in the case of power failure and power restore
After a power failure, the device starts back at zero with the calculation of the power demand
of the total active power and total reactive power.
Counter statuses and maximum/minimum values are written from the volatile to the non-
volatile memory at the following intervals:
Counter values Every 5 mins.
Maximum/minimum values Every 5 secs., if available
3.8 Digital inputs and outputs
SENTRON PAC3200 has:
one multifunctional digital input,
one multifunctional digital output.
Digital output
The following functions can be assigned to the digital output:
Energy pulse output, programmable for active energy pulses or reactive energy pulses
Indication of the direction of rotation
Displaying the operating status of the SENTRON PAC3200
Signaling limit violations
Switching output for remote control via the interface
Energy pulse output
The digital output supplies a number of pulses proportional to the energy measured.
Figure 3-6 Energy pulse output
The digital output is passive and implemented exclusively as a switch.
Implementation of the pulse function corresponds to the IEC 62053-31 standard.