Description
3.9 Ethernet port
SENTRON PAC3200
46 Manual, 02/2008, A5E01168664B-04
3.9.7 Modbus status parameters with the function code 0x02
Status parameters
You can use the MODBUS function code 0x02 on all the status parameters listed below.
Table 3-10 Status parameters
Offset Number of
registers
Name Format Value range Access
0 0 Limit 0 status Bit R
1 0 Limit 1 status Bit R
2 0 Limit 2 status Bit R
3 0 Limit 3 status Bit R
4 0 Limit 4 status Bit R
5 0 Limit 5 status Bit
0 =
No limit violation
1 =
Limit violation
R
50 0 Limit Logic status Bit R
108 0 Relevant parameter changes Bit R
109 0 Upper or lower limit violation Bit R
110 0 Maximum pulse rate exceeded Bit R
111 0 Restart of the device Bit R
112 0 Resetting of energy counter by user Bit R
116 0 Module slot 1 Bit R
117 0 Maximum pulse rate exceeded Bit R
124 0 No synchronization pulse Bit R
125 0 Device Configuration menu is active Bit R
126 0 Voltage overload Bit R
127 0 Current overload Bit R
200 0 Digital input 0 Bit R
300 0 Digital output 0 Bit
0 =
Not active
1 =
active
R
See also
Modbus measured variables with the function codes 0x03 and 0x04 (Page 40)