Description
3.9 Ethernet port
SENTRON PAC3200
48 Manual, 02/2008, A5E01168664B-04
Table 3-12 Settings parameter for the digital input
Offset Number of
registers
Name Unit Format Value range Access
0 = Status only
1 = Pulse input
2 = High tariff/low tariff
switch
50025 2 "Action" mode - unsigned long
3 = DEMAND
synchronization
RW
0 = Import kWh
1 = Export kWh
2 = Import kvarh
50029 2 "Pulse input" mode - unsigned long
3 = Export kvarh
RW
50031 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 999 RW
Table 3-13 Settings parameter for the digital output
Offset Number of
registers
Name Unit Format Value range Access
50033 2 Switching function
Assignment to a vector
group
- unsigned long 0 ... 99 RW
0 = Off
1 = Device on
2 = Remote output
3 = Direction of
rotation
4 = Limit violation
50035 2 "Action" mode - unsigned long
5 = Energy pulse
RW
0 = Limit Logic
1 = Limit 0
2 = Limit 1
3 = Limit 2
4 = Limit 3
5 = Limit 4
50037 2 "Limit violation" mode - unsigned long
6 = Limit 5
RW
0 = Import kWh
1 = Export kWh
2 = Import kvarh
50041 2 "Energy pulse" mode - unsigned long
3 = Export kvarh
RW
50043 2 Pulses per unit (pulses
per 1000 Wh / VARh)
- unsigned long 1 ... 999 RW
50045 2 Pulse length ms unsigned long 30 ... 500 RW