Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01
131
51712 1 DO 0.0 Type of use – Unsigned
short
0 … 5
0 = No action
1 = Device active
2 = Switching output
3 = Direct. of rotation
4 = Limit value
RW
51713 1 DO 0.0 Limit value index – Unsigned
short
0 … 6
0 = Comb. limit
1 = Limit0
2 = Limit1
3 = Limit2
4 = Limit3
5 = Limit4
RW
51715 1 DO 0.0 Index – Unsigned
short
0 … 3
0 = Import kWh
1 = Export kWh
2 = Import kvarh
RW
51716 1 DO 0.0 Pulses per kWh/kvarh – Unsigned
1 … 4000 RW
51717 1 DO 0.0 Pulse length – Unsigned
30 … 500 RW
51718 1 DO 0.0 Timeout – Unsigned
short
0.1 … 18000
Digital output remote timeout
1 … 18000 s, 0 = Disables
RW
51719 1 DO 0.0 Pulse divider – Unsigned
short
0 … 3
0 = 1 kWh
1 = 10 kWh
2 = 100 kWh
RW
51720 1 DO 0.1 Group assignment – Unsigned
0 … 99 RW
51721 1 DO 0.1 Type of use – Unsigned
short
0 … 5
0 = No action
1 = Device active
2 = Switching output
3 = Direction of rotation
4 = Limit value
RW
51722 1 DO 0.1 Limit value index – Unsigned
short
0 … 6
0 = Comb. limit
1 = Limit0
2 = Limit1
3 = Limit2
4 = Limit3
5 = Limit4
RW