Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
131
PULSES PER
UNIT
The field is available when the action "PULSE INPUT" is selected.
Number of pulses that must be received per unit in order for the
counter to be incremented by "1". The reference unit is defined in the
"UNIT" field.
Range: 1 to 999
Default value: 1
EDGES PER
UNIT
The field is available when the action "ENERGY PULSE" is selected.
Number of edges that must be received per unit in order for the
counter to be incremented by "1". The reference unit is defined in the
"UNIT" field.
Range: 1 to 999
Default value: 1
UNIT Visible when the action "PULSE INPUT" is selected.
Unit to be counted when counting the pulses or edges received:
kWh (active energy)
kVARh (reactive energy)
TEXT
"TEXT" stands for a user definable unit, e.g. m
3
/h or pieces. The text
sequence used to name the unit must be defined via the
communication interface. The defined text sequence is displayed in
the "TEXT" field when you select "TEXT".
TEXT Text sequence used to name the unit to be counted. See "UNIT"
field.
9.2.8 Communication
Device settings for network communication.
Call: "SETTINGS > COMMUNICATION"
Figure 9-8 "COMMUNICATION" device setting
A change to the TCP/IP addresses only becomes effective after the device has been
restarted.
If you exit the "COMMUNICATION" device setting with the F1 key
, the device asks if
you want to restart.
● F1 key
: Do not execute a restart. Address changes are saved on the device but do
not become effective.
● F4 key
: Execute a restart. Address changes become effective.