Technical data
11.1 Technical data
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
159
Dimensi
ons
[mm] [inch]
D
VA
W
L1
L2
L3
3 ... 4
0,75 ... 1,0
≤ 8
≤ 24
≤ 20
≥ 8
0.118 ... 0.157
0.029 ... 0.039
≤ 0.314
≤ 0.944
≤ 0.787
≥ 0.314
Dimensions of the ring lug
/
/
/
'
:
6
Connection bolt M3 to M4 #5 ... #8
Conductor cross section
depending on the ring lug used
1.0 to 6.0 mm
2
). AWG 18 to 10
The national standards for ring lugs must be
observed, e.g. UL listed under ZMVV /7, CSA,
DIN 46237, IEC 60352-2
Please observe the information of the ring lug
manufacturer as well as IEC 60352-2 with regard
to the creation of suitable crimp connections.
The ring lugs must be installed in parallel with
each other.
Connection screws
Tightening torque 0.8 ... 1.2 Nm
7 ... 10.3 lbf·in
With vertical screwing
force
30 N
6.75 lbf
Tool Screwdriver PZ2
cal. ISO 6789
Crimping or pressing tool according to
manufacturer's information for ring lugs