Siemens SENTRON PAC4200 - Structure - Limit Values with the Function Codes 0 X01 and 0 X02

Siemens SENTRON PAC4200
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.3 MODBUS
SENTRON PAC4200
204 Manual, 09/2008, A5E02316180B-01
A.3.3 Structure - Limit values with the function codes 0x01 and 0x02
Structure of the limit values
Table A- 4 Modbus Offset 203, Register 2: Limit Violations
Byte Bit Status Bit mask Value range Access
3 0 Limit 0 0x00000001 R
3 1 Limit 1 0x00000002 R
3 2 Limit 2 0x00000004 R
3 3 Limit 3 0x00000008 R
3 4 Limit 4 0x00000010 R
3 5 Limit 5 0x00000020 R
3 6 Limit 6 0x00000040 R
3 7 Limit 7 0x00000080 R
2 0 Limit 8 0x00000100 R
2 1 Limit 9 0x00000200 R
2 2 Limit 10 0x00000400 R
2 3 Limit 11 0x00000800 R
0 0 Limit Logic 0x01000000 R
0 1 Function block 1 at logic inputs 1 ... 4 0x02000000 R
0 2 Function block 2 at logic inputs 1 ... 4 0x04000000 R
0 3 Function block 3 at logic inputs 1 ... 4 0x08000000 R
0 4 Function block 4 at logic inputs 1 ... 4 0x10000000
0 =
No limit violation
1 =
Limit violation
R
See also
Measured variables without a time stamp with the function codes 0x03 and 0x04 (Page 196)