Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
213
A.3.9 Minimum values with a time stamp and the function codes 0x03 and 0x04
Addressing the minimum values with a time stamp
Table A- 14 Available measured variables: Minimum values with time stamp
Offset Number
of
registers
Name Format Unit Value range Access
6001 6 Minimum Voltage a-n with Time Float + time stamp V - R
6007 6 Minimum Voltage b-n with Time Float + time stamp V - R
6013 6 Minimum Voltage c-n with Time Float + time stamp V - R
6019 6 Minimum Voltage a-b with Time Float + time stamp V - R
6025 6 Minimum Voltage b-c with Time Float + time stamp V - R
6031 6 Minimum Voltage c-a with Time Float + time stamp V - R
6037 6 Minimum Current a with Time Float + time stamp A - R
6043 6 Minimum Current b with Time Float + time stamp A - R
6049 6 Minimum Current c with Time Float + time stamp A - R
6055 6 Minimum Apparent Power a with Time Float + time stamp VA - R
6061 6 Minimum Apparent Power b with Time Float + time stamp VA - R
6067 6 Minimum Apparent Power c with Time Float + time stamp VA - R
6073 6 Minimum Active Power a with Time Float + time stamp W - R
6079 6 Minimum Active Power b with Time Float + time stamp W - R
6085 6 Minimum Active Power c with Time Float + time stamp W - R
6091 6 Minimum Reactive Power a (VARn) with
Time
Float + time stamp VAR - R
6097 6 Minimum Reactive Power b (VARn) with
Time
Float + time stamp VAR - R
6103 6 Minimum Reactive Power c (VARn) with
Time
Float + time stamp VAR - R
6109 6 Minimum Total Reactive Power a (VARtot)
with Time
Float + time stamp VAR - R
6115 6 Minimum Total Reactive Power b (VARtot)
with Time
Float + time stamp VAR - R
6121 6 Minimum Total Reactive Power c (VARtot)
with Time
Float + time stamp VAR - R
6127 6 Minimum Reactive Power a (VAR1) with
Time
Float + time stamp VAR - R
6133 6 Minimum Reactive Power b (VAR1) with
Time
Float + time stamp VAR - R
6139 6 Minimum Reactive Power c (VAR1) with
Time
Float + time stamp VAR - R
6145 6 Minimum Power Factor a with Time Float + time stamp - 0 ... 1 R
6151 6 Minimum Power Factor b with Time Float + time stamp - 0 ... 1 R
6157 6 Minimum Power Factor c with Time Float + time stamp - 0 ... 1 R
6163 6 Minimum cos φ a with Time Float + time stamp cos φ
a
- R