EasyManua.ls Logo

Siemens SENTRON PAC4200 - Page 214

Siemens SENTRON PAC4200
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.3 MODBUS
SENTRON PAC4200
214 Manual, 09/2008, A5E02316180B-01
Offset Number
of
registers
Name Format Unit Value range Access
6169 6 Minimum cos φ b with Time Float + time stamp cos φ
b
- R
6175 6 Minimum cos φ c with Time Float + time stamp cos φ
c
- R
6181 6 Minimum Displacement Angle a with Time Float + time stamp φ - R
6187 6 Minimum Displacement Angle b with Time Float + time stamp φ - R
6193 6 Minimum Displacement Angle c with Time Float + time stamp φ - R
6217 6 Minimum Line Frequency with Time Float + time stamp - 45 ... 65 R
6223 6 Minimum 3-Phase Average Voltage ph-n
with Time
Float + time stamp V - R
6229 6 Minimum 3-Phase Average Voltage ph-ph
with Time
Float + time stamp V - R
6235 6 Minimum 3-Phase Average Current ph-ph
with Time
Float + time stamp A - R
6241 6 Minimum Total Apparent Power with Time Float + time stamp VA - R
6247 6 Minimum Total Active Power with Time Float + time stamp W - R
6253 6 Minimum Total Reactive Power (VARn)
with Time
Float + time stamp VAR - R
6259 6 Minimum Total Power Factor (VARn) with
Time
Float + time stamp - - R
6265 6 Minimum Neutral Current with Time Float + time stamp A - R
6271 6 Minimum Total Reactive Power (VARtot)
with Time
Float + time stamp VAR - R
6277 6 Minimum Total Reactive Power (VAR1)
with Time
Float + time stamp VAR - R
6283 6 Min. Sliding Window Demand Voltage a-n
with Time
Float + time stamp V - R
6289 6 Min. Sliding Window Demand Voltage b-n
with Time
Float + time stamp V - R
6295 6 Min. Sliding Window Demand Voltage c-n
with Time
Float + time stamp V - R
6301 6 Min. Sliding Window Demand Voltage a-b
with Time
Float + time stamp V - R
6307 6 Min. Sliding Window Demand Voltage b-c
with Time
Float + time stamp V - R
6313 6 Min. Sliding Window Demand Voltage c-a
with Time
Float + time stamp V - R
6319 6 Min. Sliding Window Demand Current a
with Time
Float + time stamp A - R
6325 6 Min. Sliding Window Demand Current b
with Time
Float + time stamp A - R
6331 6 Min. Sliding Window Demand Current c
with Time
Float + time stamp A - R
6337 6 Min. Sliding Window Demand Apparent
Power a with Time
Float + time stamp VA - R
6343 6 Min. Sliding Window Demand Apparent
Power b with Time
Float + time stamp VA - R

Table of Contents

Other manuals for Siemens SENTRON PAC4200

Related product manuals