Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
239
A.3.15 I&M settings
Addressing the settings for the I&M data
Table A- 23 Settings for the I&M data
Offset Number
of
registers
Name Format Unit Applicable
MODBUS
function codes
Value range Access
64001 27 IM Data PAC4200 stIM0 -
• 0x03
• 0x04
- R(W)
64028 89 IM 0 to IM 4 Data PAC4200 stIM14 -
• 0x03
• 0x04
• 0x10
- RW
64117 27 IM Data Module Interface 1 stIM0- -
• 0x03
• 0x04
- R(W)
64144 27 IM Data Module Interface 2 stIM0 -
• 0x03
• 0x04
- R(W)
A.3.16 Commands with the function code 0x06
Addressing the commands
Table A- 24 Commands
Offset Number of
registers
Name Format Applicable
MODBUS
function codes
Value range Access
60000 1 Device reset to factory
default settings
Unsigned
short
0x06 - W
60001 1 Device reset (no change
of IP address)
Unsigned
short
0x06 - W
60002 1 Reset maximum values Unsigned
short
0x06 0 W
60003 1 Reset minimum values Unsigned
short
0x06 0 W
0 = All
1 = Active energy
import tariff 1
2 = Active energy
import tariff 2
3 = Active energy
export tariff 1
60004 1 Reset energy counters Unsigned
short
0x06
4 = Active energy
export tariff 2
W