3.12 Serial gateway
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
47
Configuration of the gateway
SENTRON PAC4200 must be configured for using the serial gateway.
Start up the SENTRON PAC RS485 expansion module on the SENTRON PAC4200.
Set the communication parameters for operating the RS485 bus below the gateway.
These settings are possible on the display of SENTRON PAC4200 or in the software.
You can find information about setting parameters in the documentation for the SENTRON
PAC RS485 expansion module.
Addressing the target devices
The following address information is required in the management software in order to
address a device via the serial gateway of SENTRON PAC4200:
IP address of SENTRON PAC4200
Gateway port
Port 17002 if the RS485 bus is connected to the "MOD1" slot
Port 17003 if the RS485 bus is connected to the "MOD2" slot
Bus address of the target device, e.g. MODBUS address