Siemens SENTRON VL 160 - Detailed Protection Parameter Adjustment; Adjusting Current and Time-Based Settings; Ground Fault and Thermal Memory Configuration

Siemens SENTRON VL 160
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3ZX1012-0VL21-1EA1 11
BOTTOM OF LIST
= NO
DATA
ex: 3VL93256CH35 ; I
n
= 250 A , I
r
= 100 A
CHANGING PROTECTION SETTINGS
TOP OF LIST
CHANGE PROTECTION
CHANGE SAVED
CHANGE NOT SAVED
CONTINUOUS AMPS SETTING 100 AMP
CONTINUOUS AMPS SETTING 250 AMP
CONTINUOUS AMPS
CHANGE SAVED
CHANGE NOT SAVED
LONG TIME DELAY SETTING 2.5 SEC
LONG TIME DELAY SETTING 30 SEC
LONG TIME DELAY
CHANGE SAVED
CHANGE NOT SAVED
SHORT TIME DELAY OFF
SHORT TIME DELAY ON
CHANGE SAVED
CHANGE NOT SAVED
SHORT TIME PICKUP = 150 A
SHORT TIME PICKUP = 1000 A
SHORT TIME PICKUP
CHANGE SAVED
CHANGE NOT SAVED
SHORT TIME DELAY SETTING .100 SEC
SHORT TIME DELAY SETTING .500 SEC
SHORT TIME DELAY
CHANGE SAVED
CHANGE NOT SAVED
SHORT TIME MODE FIXED
SHORT TIME MODE (I^2)T
CHANGE SAVED
CHANGE NOT SAVED
INSTANTANEOUS CURRENT = 312 AMPS
INSTANTANEOUS CURRENT = 2750 AMPS
IOC AMPS
CHANGE SAVED
CHANGE NOT SAVED
THERMAL MEMORY IS OFF
THERMAL MEMORY IS ON
CHANGE SAVED
CHANGE NOT SAVED
PREALARM IS OFF
PREALARM IS ON
PREALARM ENABLE
CHANGE SAVED
CHANGE NOT SAVED
PREALARM SET AT 80 AMPS
PREALARM SET AT 100 AMPS
TOP OF LIST
SHORT TIME
SHORT TIME MODE
THERMAL MEMORY
PREALARM
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= NO
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
= YES
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
SAVE CHANGES ?
GRND FAULT TYPE
GF PICKUP
GF DELAY MODE
GF DELAY
CHANGE SAVED
CHANGE SAVED
CHANGE SAVED
CHANGE SAVED
CHANGE NOT SAVED
CHANGE NOT SAVED
CHANGE NOT SAVED
CHANGE NOT SAVED
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
DATA
GROUND FAULT IS GND RESIDUAL
GROUND FAULT IS GND RETURN
GROUND FAULT PICKUP= 312 A
GROUND FAULT PICKUP= 2750 A
GF DELAY MODE IS FIXED
GF DELAY MODE IS (I^2)T
GF DELAY SETTING= .100 SEC
GF DELAY SETTING= .500 SEC