29SICAM P850/P855 7KG85xx, Product Information
E50417-B1050-C482-A3, Edition 03.2013
13 Interfaces
Figure 13-1 Terminals on the Terminal Side
Terminals for supply voltage (H), inputs for current
measurement (E), inputs for voltage measurement (F),
binary outputs (G) on the terminal side:
Conductor cross-section 2.5 mm² (AWG 14)
with bootlace ferrule 1.5 mm² (AWG 16)
with bootlace ferrule (term. F) 2.5 mm² (AWG 14)
Tightening torque 0.4 Nm to 0.5 Nm
(3.5 in-lb to 4.5 in-lb)
RS485 interface (J) on the terminal side:
RS485 cable with plug connector (D-Sub)
Ethernet interface (Z) on the top side:
Ethernet patch cable with plug connector (RJ45)
DANGER
Danger due to high voltages
Non-observance will lead to death or serious injury.
 The grounding on the device always has to be con-
nected to the protective conductor terminal (termi-
nal block H).