[sc_config_load_profile, 1, en_US]
Figure 5-4 Configuration Tab, Load Profile
•
Configure the respective parameters according to the following table.
Table 5-2 Settings for Load Profile
Parameter Default Setting Setting Range
Subperiod time 15 min 1 min to 6 min in 1-min steps,
10 min, 12 min, 15 min, 20 min, 30 min, 60 min
Number of subperiods
9
1 1 to 5
Synchronization source Internal clock None
Protocol
Internal clock
Kind of used reactive power Q1 Q1
Qn
Qtot
NOTE
Changing the number and length of the subperiods deletes the load-profile buffer.
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to Table 2-3).
•
Click Activation.
Value View of the Load Profile
To display the values of the load profile in the Value view tab, proceed as follows:
•
In the navigation window, click Load profiles.
In the decimal separator, you can select whether you want to display the load-profile data with comma or
decimal point after the download.
9
Number = 1: Fixed Block method: The lengths of the subperiod and of the measuring period are identical; Number = 2 to 5: Rolling
Block method; Length of the subperiod: The length of the subperiod is an integer part of a full hour; Length of measuring period: The
length of the measuring period cannot be configured directly. It is defined as the product of the length of the subperiod and the
number of subperiods: Length of measuring period = n x length of subperiod; n = number of subperiods
Energy Management
5.1 Load Profile
SICAM, SICAM P850/P855 7KG85X, Manual 105
E50417-H1040-C482-A9, Edition 03.2022