To download the load profile, proceed as follows:
•
Click Download load profile.
The File Download dialog opens. You can save the CSV file. For more information, refer to 7.3.3 Single
File Download.
NOTE
The file extension must be .csv.
Configuration via Display
Submenu Load Profile
NOTE
If you select the Load profile parameter, the following message is displayed first:
Changing these parameters resets the load profile!
To confirm, press the softkey F4 (Ok).
[dw_submenu_load_profile_Q100, 1, en_US]
Figure 5-5 Submenu Load Profile
Table 5-3 Settings for the Load Profile
Parameter Default Setting Setting Range
Subperiod time 15 min 1 min to 6 min in 1-min steps,
10 min, 12 min, 15 min, 20 min, 30 min,
60 min
No. of subperiods 1 1 to 5
5.1.3
Energy Management
5.1 Load Profile
106 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022