Table 5-5 Settings for Tariffs (TOU)
Parameter Default Setting Setting Range
Synchronization source Protocol
Protocol
10
Calendar
The following parameters are available only when Synchronization source is set to Calendar.
Season 1 Start 01-01 01-01 to 12-31
Season 1 End 06-30 01-01 to 12-31
Season 2 Start 07-01 Not settable The rest days of the full year
Season 2 End 12-31
Weekend Setting Thursday and Friday Sunday to Saturday, max. 2 days
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 1 Start
00:00 00:00 to 23:45
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 1 End
24:00 00:15 to 24:00
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 2 Start
00:00 00:15 to 23:45
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 2 End
24:00 00:30 to 24:00
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 1 Active
No
11
Yes
No
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Period 2 Active
No Yes
No
Season x (x = 1 or 2) Tariff y (y
= 1 to 8) Workday/ Weekend
Selection
Every Day Every Day
Workday
Weekend
Coverage Check Pass
Fail (with gap)
Fail (with overlap)
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to Table 2-3).
•
Click Activation.
Synchronization Source = Calendar
When Synchronization source is set to Calendar:
•
If the coverage check passes, all the coverage check bars are show in green, see Figure 5-10.
•
If the coverage check fails, the coverage check bars are show in other colors, see Figure 5-11. The button
Send is disabled. You must reconfigure the parameters.
10
In this case, the protocol Modbus TCP can control tariff 1 to tariff 8.
11
The default settings of Tariff 1 Period 1 Active for 2 seasons are checked.