Table 6-5 Settings for Flicker
Parameter Default Setting Setting Options
Flicker lamp model 230 V 230 V
120 V
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to Table 2-3).
Click Activation.
Value View of the Flicker
To display the flicker values in the Value view tab, proceed as follows:
In the navigation window, click Flicker.
[sc_value_view_flicker, 1, en_US]
Figure 6-6 Value View Tab, Flicker
To display the aggregation values of the flicker in the Value view tab, proceed as follows:
In the navigation window, click Records.
Configure the respective parameters according to 6.6.2 Configuration and Value View via Web Pages.
Select Long term flicker or Short term flicker as the Measurement source.
Evaluation via Display
Submenu Flicker
In the main menu, click Short flicker ph-n, Short flicker ph-ph, Long flicker ph-n, or Long flicker ph-ph.
6.2.3
Power Quality
6.2 Flicker
122 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022