EasyManua.ls Logo

Siemens SICAM 7KG85X - Frequency Events; Configuration and Value View Via Web Pages

Siemens SICAM 7KG85X
281 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency Events
Configuration and Value View via Web Pages
Configuring the Frequency Events
[sc_Param frequency events, 1, en_US]
Figure 6-17 Configuration Tab, Frequency Events
To change the frequency event settings in the Configuration tab, proceed as follows:
In the navigation window, click Event records
Configure the respective parameters according to the following table.
Table 6-10
Settings for Frequency Events
Parameter Default Setting Setting Range
Underfrequency threshold 1 % 0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
Overfrequency threshold 1 % 0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to Table 2-3).
Click Activation.
Value view of the Frequency Events
To display the frequency event values in the Value view tab, proceed as follows:
In the navigation window, click Events.
Configure the respective parameters according to the following table.
Table 6-11
Settings for Viewing the Frequency Events
Parameter Default Setting Setting Range
Event record type Frequency event Voltage event
Frequency event
Voltage unbalance event
Start time One hour before the current date/
time
You can edit the text box directly or
select the start time from the
calendar.
6.4.3
6.4.3.1
Power Quality
6.4 Event Records
130 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022