[dw_q100_Waveform_example, 1, en_US]
Figure 6-20
Example of Waveform Recording
The following table shows which measured quantities can be recorded in COMTRADE files when a corre-
sponding trigger function is activated.
Table 6-15
Recording and Evaluation
Recorder Routing Measured Quantities COMTRADE
Voltage
13
Va x
Vb x
Vc x
Vab x
Vbc x
Vca x
V
N
x
Current
14
Ia x
Ib x
Ic x
13
For the 3-wire, 3-phase network type, voltage in the phase-to-phase channel is recorded; for the 4-wire, 3-phase network type,
voltage in the phase-to-neutral channel is recorded.
14
Current channels can be recorded when the current trigger is activated.
Power Quality
6.5 Waveform Records
SICAM, SICAM P850/P855 7KG85X, Manual 135