Parameter Default Setting Setting Range
Tolerance unit Percentage Percentage
Numerical
Upper threshold 110.00 % of the primary nominal
voltage
100.0 % to 120.0 % of the primary
nominal voltage
Lower threshold 90.00 % of the primary nominal voltage 0.00 % to 99.99 % of the primary
nominal voltage
Hysteresis 2.00 % of the primary nominal voltage 0.0 % to 50.0 % of the primary nominal
voltage
Current trigger limits
Trigger active No No
Yes
Tolerance unit Percentage Percentage
Numerical
Upper threshold 110.00 % of nominal current 5.0 % to 200.0 % of the nominal
current
Lower threshold 90.00 % of nominal current 0.00 % to 99.99 % of the nominal
current
Hysteresis 2.00 % of the nominal current 0.0 % to 50.0 % of the nominal current
Waveform capture setting
Total recording duration 2.0 s 0.2 s to 3.0 s, increments of 0.2 s
Pretrigger ratio 10% 0 % to 30 %, increments of 5 %
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to Table 2-3).
Click Activation.
Error Information
If the set value is out of the range, a red error message Note: Please consider the setting ranges! appears
and the value changes back to the default setting.
If the set values do not follow the setting rules, a red error message Note: Consider setting rules: 'upper
threshold > lower threshold' and (upper threshold - lower threshold) > 2 * hysteresis appears and the
value changes back to the previous setting.
Value View of the Waveform Records
You cannot view the waveform records triggered by the other sources via the Web browser, but you can
download them. For more information, refer to chapter 7.3 File Download.
During the download progress, the selected files are stored by the browser. You can use the software SIGRA to
display the transmitted record data. For more information on SIGRA, contact the Siemens Hotline.
Clearing of Waveform Records
To clear waveform records, refer to chapter 7.2 Clearing of Data.
6.5.3
Power Quality
6.5 Waveform Records
SICAM, SICAM P850/P855 7KG85X, Manual 137
E50417-H1040-C482-A9, Edition 03.2022

Table of Contents

Other manuals for Siemens SICAM 7KG85X