[sc_freq_meas_20min, 1, en_US]
Figure 6-23 Example 2 for Measurement Records, Frequency Measurement of 10 Seconds, and Record
Duration of 1 Hour
Recording and Evaluation of the Measured Quantities
NOTE
The voltage is recorded in the following network types:
•
1-phase network
•
3P4W (3 phases/4 wires): balanced and unbalanced
•
3P3W (3 phases/3 wires): balanced, unbalanced (2 * l), and unbalanced (3 * l)
Table 6-17 Recording and Evaluation of the Measured Quantities
Measured Quantities
AVG Max. Value Min. Value
PQDIF
Frequency
10 s freq
(fixed 10 s freq.)
x
15
– –
f
(system frequency based on
10/12 cycles)
x x x
f
(system frequency based on 10 s)
x x x
Voltage (measurement intervals 1 min, 10 min)
Va x x x
Vb x x x
Vc x x x
V
N
x x x
Vavg x – –
Vavg ph-ph x – –
Vab x x x
Vbc x x x
15
According to IEC 61000-4-30, the frequency is permanently defined with 10 s mean-value recording.
Power Quality
6.6 Measurement Records
SICAM, SICAM P850/P855 7KG85X, Manual 139
E50417-H1040-C482-A9, Edition 03.2022