Table 6-18 Settings for Measurement Records (only SICAM P855)
Parameter Default Setting Setting Range
Average intervals - Frequency 10 s fixed
Short term flicker 10 min fixed
Long term flicker 2 h fixed
Average interval - Voltage /
Unbalance / THDS / Harmonics
10 min 1 min
10 min
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics Odd Even
Odd
All
File generation every:
(corresponds to the setting of
the Average interval parameter)
The created PQDIF files can be
downloaded via the Web pages
or the IEC 61850 protocol.
24 h At average interval: File generation every:
1 min 2 h (fixed)
10 min 2 h
24 h
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to Table 2-3).
•
Click Activation.
Value View of the Measurement Records
To display the measurement records in the Value view tab, proceed as follows:
•
In the navigation window, click Records.
•
Configure the respective parameters in the list boxes according to the following tables.
Table 6-19
Settings for Viewing the Measurement Records
Parameter Default Setting Setting Range
Record type Measurement records Trend records
Measurement records
Measurement Records
Start time Current time Any with calendar function Time format:
depends on date/time format config.
End time Not settable
One hour after Start time
Measurement source Frequency 10 s Acc. to list box
Measurements f - 10 s The selectable Measurements depend on the
selected Measurement Source.
Power Quality
6.6 Measurement Records
142 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022