[sc_Get_device_configuration, 2, en_US]
Figure 9-30 Configuration Tab, Get Default Configuration
The factory settings (= passive set of parameters) are restored, and the status of the "parameter set for config-
uration" changes from "equal to active" to "modified".
Open Configuration from File
If you have selected Open configuration from file in the Configuration tab, you can open an existing file in a
folder.
Proceed as follows:
[sc_Open-configuration-from-file, 3, en_US]
Figure 9-31 Configuration Tab, Open Configuration from File
Click Choose file.
Select the desired file (extension .cfg) in the directory.
i
i
NOTE
The file name has the following restrictions:
Maximum 8 characters
Only containing:
Letters: a to z, A to Z
Numbers: 0 to 9
Hyphen (-) and underline (_)
Click Open.
The selected path is inserted in the Browse field, Figure 9-31.
Click Open.
The device configuration from the CFG file is loaded.
9.11.2.10
Commissioning and First Steps
9.11 Operation via PC
SICAM, SICAM P850/P855 7KG85X, Manual 225
E50417-H1040-C482-A9, Edition 03.2022