Air humidity data Mean relative humidity per year ≤ 75 %
Maximum relative humidity 95 % 30 days a year
Condensation during operation Not permitted
Condensation during transport and
storage
Permitted
Altitude and operation site Max. altitude above sea level 2000 m
Operating site Indoors use
Climatic Stress Tests
Standards: IEC 60068
Dry cold:
IEC 60068-2-1 test Ad
Dry heat during operation, storage, and transport:
IEC 60068-2-2 test Bd
Damp heat:
IEC 60068-2-78 test Ca
Change of temperature:
IEC 60068-2-14 test Na and Nb
General Data
Battery
Type PANASONIC CR2032 or
VARTA 6032 101 501
Voltage 3 V
Capacity 230 mAh
Typical life For operation with permanently
applied supply voltage:
10 years
For operation with sporadically
interrupted supply voltage:
A total of 2 months over a 10-year
period
Internal memory Capacity 2 GB
Degree of protection
DIN rail housing IP20
Panel flush mounting (front) IP40 (with display, without door)
IP51 (with display and door)
Terminals IP2x
12.1.5
Technical Data
12.1 Technical Data
SICAM, SICAM P850/P855 7KG85X, Manual 249
E50417-H1040-C482-A9, Edition 03.2022