Test Data
Reference Conditions according to IEC 62586-1 for Determining Test Data
Ambient temperature 23 °C ± 2 °C
Relative humidity 40 % to 60 % RH
Supply voltage V
PS
± 1 %
Phases (3-wire network) 3
External continuous magnetic fields DC field: ≤ 40 A/m
AC field: ≤ 3 A/m
DC components V/I None
Signal waveform Sinus
Frequency 50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Voltage magnitude Udin ± 1 %
Flicker Pst < 0.1 %
Unbalance (all channels) 100 % ± 0.5 % of Udin
Harmonic 0 % to 3 % of Udin
Interharmonic 0 % to 0.5 % of Udin
Electrical Tests
Standards
Standards
IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Inputs/Outputs
Insulation Rated Voltage ISO Test Voltage Category
Current measurement
inputs
Reinforced 150 V AC 2.3 kV Cat. III
Voltage measurement
inputs
Reinforced 480 V Surge voltage
9.76 kV
Cat. III
Supply voltage Reinforced 300 V DC 3.125 kV Cat. III
Binary outputs Reinforced 300 V AC 3.536 kV Cat. III
Ethernet interface Function < 50 V DC 700 V
RS485 interface Function < 50 V DC 700 V
EMC Tests for Immunity (Type Tests)
Standards
IEC EN 61000-6-2
For more standards see also individual functions
Electrostatic discharge,
Class III, IEC 61000-4-2
6 kV contact discharge
8 kV air discharge, both polarities
150 pF, Ri = 330 Ω with connected Ethernet cable
12.2
12.2.1
12.2.2
Technical Data
12.2 Test Data
250 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022