Operational Indications
Operational Indications
Indication Description Notes
Device OK The device startup was successful. Indication ON: Device ready
Battery Failure Battery voltage < 2.7 V or no
battery inserted
Indication ON: Battery failure
Time Synchronization
Error
Error during the time synchroniza-
tion from the NTP server or
fieldbus
Indication OFF: At least 1 time message was received
during the set timer (Error indication after). The time
stamp is set when the first valid time information or time
synchronization is received.
Indication ON: No time message was received during the
set timer (Error indication after).
The time stamp is set after the Error indication after timer
has expired and no synchronization message was received.
Parameter range: see chapter 13.2.2 Date and Time.
Error sources with NTP or fieldbus: Error indication after
timer expires and no synchronization message was received
Error during internal time synchro-
nization
Indication ON: RTC time invalid (during device start in case
of battery failure)
Indication OFF: After setting the clock via HTML
During battery failure at device startup
Default IP Address The device has started with a
default IP address after pressing
the push-button for more than 3 s
during operation.
Indication ON: The push-button was pressed and default IP
is set in the device.
Primary NTP Server
Error
Faulty or no response from the
primary NTP server
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Secondary NTP Server
Error
Faulty or no response from the
secondary NTP server
Indication ON: Error
Indication OFF: Valid time messages have been received for
a configured period.
Only for time synchronization via Ethernet NTP
Daylight Saving Time Switching between daylight saving
time/standard time
Indication ON: Daylight saving time
Indication OFF: Standard time
Ethernet Link Error Ethernet connection error Indication ON: Error
Indication OFF: Ethernet link recognized
Modbus TCP OK
(Modbus TCP Server)
At least 1 Modbus TCP server
connection has received Modbus
messages.
Indication ON: At least 1 Modbus message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No Modbus message was received during
the set communication supervision time
IEC 61850 Communi-
cation OK
Communication via protocol IEC
61850 is correct.
Indication ON: At least one message was received during
the set monitoring time. The time stamp is set when the
first valid message is received.
Indication OFF: No message was received during the set
monitoring time.
13.1
13.1.1
Operational Indications and Operating Parameters
13.1 Operational Indications
260 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022