Indication Description Notes
Modbus Serial OK
(Modbus RTU (Slave))
The Modbus serial communication
has received a valid Modbus
message.
Indication ON: At least 1 serial message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No serial message was received during the
set communication supervision time.
IEC 60870-5-103 OK Communication via protocol IEC
60870-5-103 is correct.
Indication ON: At least 1 serial message was received
during the set communication supervision time. The time
stamp is set when the first valid message is received.
Indication OFF: No serial message was received during the
set communication supervision time.
Settings Load Starting to change the parameters
of the passive set of parameters.
Indication ON: Start of changes
Indication OFF: Changes complete
Settings Check The passive set of parameters is to
be activated; the internal param-
eter check is running.
Indication ON: Check started
Indication OFF: Check complete
Settings Activate The passive set of parameters is
enabled and the device works with
these parameters.
Indication ON: Activation started
Indication OFF: Activation complete
Limit Violation x Indication that a parameterized
limiting value has been violated
Indication ON: The limit of the monitored measured value
has been violated or no measured value is parameterized as
input of the limiting value.
Indication OFF: The limit of the monitored measured value
is not violated.
Message invalid: The monitored measured value is invalid
(for example, frequency at V < 15 % of V
rated
).
x = 1 to 16
Indication 1 from
Remote
Status of the indications that can
be set to control the LEDs and the
binary outputs via the communica-
tion.
Indication ON: ON
Indication OFF: OFF
Message invalid: Not yet updated via the communication or
again invalid via the communication
Indication 2 from
Remote
Reset Energy The energy counters were reset. Indication ON: Energy counters reset
Rotating Field Clock-
wise
Indication of rotation voltage Indication ON: Phase sequence Va-Vb-Vc, rotation clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases inter-
changed); rotation counter-clockwise
Indication invalid: Direction of rotation cannot be calcu-
lated (for example, no voltage applied)
Group indication x Up to 4 single-point indications can
be linked logically and combined to
a group indication.
A total of 4 group indications can be parameterized.
x = 1 to 4
Voltage Event Avail-
able
Indication of a voltage event Voltage dip, voltage swell, and voltage interruption
Voltage Dip Start Start of a voltage dip Voltage dip
Voltage Swell Start Start of a voltage swell Voltage swell
Voltage Interruption
Start
Start of a voltage interruption Voltage interruption
Voltage Unbalance
Event Available
Indication of a voltage unbalance
event
Voltage unbalance
Frequency Event Avail-
able
Indication of a frequency event Overfrequency or underfrequency
Operational Indications and Operating Parameters
13.1 Operational Indications
SICAM, SICAM P850/P855 7KG85X, Manual 261
E50417-H1040-C482-A9, Edition 03.2022