Parameter Default Setting Setting Range
Baud rate 9600 bit/s 9600 bit/s
19 200 bit/s
38 400 bit/s
Measured value range 120 %
equivalent to a measured value
range from -4096 to +4095 (-120
% to +120 %)
120 %
240 %
equivalent to a measured value
range from -4096 to +4095 (-120
% to +120 % or -240 % to +240 %)
Transmit energy No Yes (every minute)
No
Transmission of the 1st to 40th
harmonics HV and HI
No No
Yes
Cyclic sending period 50 * 100 ms 30 * 100 ms to 600 * 100 ms
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Operational Indications and Operating Parameters
13.2 Basic Functions
268 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022