Advanced Functions
Process Connections
Binary Outputs
Table 13-12 Settings for Binary Outputs
Parameter Default Setting Setting Range
Source type Indication Indication
Energy counter
Source Type Indication
Indication
23
-none- Acc. to list box
Source inverted
(can be set individually for all
relay outputs)
No No
Yes
Operating mode
24
(can be set individually for all
relay outputs)
Persistent Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating
mode (setting only possible for
operating modes Pulse and
Pulse with retrigger)
20 (* 10 ms) 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter
23
-none- Acc. to list box
Energy increase per pulse 1.00 Wh 0.10 Wh/VAh/varh to
1 000 000.00 Wh/VAh/varh
Output time for pulse operating
mode
20 * 10 ms = 200 ms 50 ms to 3 600 000 ms
LEDs
Table 13-13
Settings for LEDs
Parameter Default Setting Setting Range
RUN Device ready Not settable
ERROR -none- Errors are signaled as parameterized (only error
indications can be parameterized).
-none-
Battery failure
Ethernet link error
Time synchronization error
Primary NTP server error
Secondary NTP server
SD card error
13.3
13.3.1
13.3.1.1
13.3.1.2
23
If you select -none- as the source of an indication or energy counter, the corresponding binary output is inactive.
24
If you have selected one of the 2 Pulse types in the Operating mode list box, enter an output time x (in x *10 ms) in the Output
time for pulse operating mode field.
Operational Indications and Operating Parameters
13.3 Advanced Functions
SICAM, SICAM P850/P855 7KG85X, Manual 269
E50417-H1040-C482-A9, Edition 03.2022