EN 50160 Report (only SICAM P855)
Table 13-24 Settings for EN 50160 Report
Parameter Default Setting Setting Options
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Any text displayed in the
printout of the power-quality
report
Max. 32 characters
Power Quality Report
Evaluation mode according to EN 50160 LV&MV
EN 50160 LV&MV
EN 50160 HV
User-defined
Flagging acc. to IEC 61000-4-30 No No
Yes
Power frequency 99.5 % of the measurement should be
within a deviation of -1.0 % to 1.0 %
The settings are fixed for the
template of EN 50160 LV&MV
and EN 50160 HV.
You can edit the limiting
values in the text box directly
under the user-defined evalua-
tion mode.
100 % of the measurement should be
within a deviation of -6.0 % to 4.0 %
Power supply voltage magnitude 95 % of the measurement should be
within a deviation of -10.0 % to 10.0 %
100 % of the measurement should be
within a deviation of -15.0 % to 10.0 %
Flicker severity 95 % of the measurement should be less
than 1.0 %
Total harmonic distortion (THDS) 95 % of the measurement should be less
than 8.0 %
Voltage event interruptions Short interruption until 1-second duration
Short interruption until 3-minute duration
Long interruption longer than 3-minute
duration
Harmonic
voltages for the
template of EN
50160 LV&MV
Odd
harmonics
H3: 5.0, H5: 6.0, H7: 5.0, H9: 1.5, H11:
3.5, H13: 3.0, H15: 0.5, H17: 2.0, H19:
1.5, H21: 0.5, H23: 1.5, H25: 1.5
Even
harmonics
H2: 2.0, H4: 1.0, H6: 0.5, H8: 0.5, H10:
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
Harmonic
voltages for the
template of EN
50160 HV
Odd
harmonics
H3: 3.0, H5: 5.0, H7: 4.0, H9: 1.3, H11:
3.0, H13: 2.5, H15: 0.5, H17: u.c.
29
, H19:
u.c., H21: 0.5, H23: u.c., H25: u.c.
Even
harmonics
H2: 1.9, H4: 1.0, H6: 0.5, H8: 0.5, H10:
0.5, H12: 0.5, H14: 0.5, H16: 0.5, H18:
0.5, H20: 0.5, H22: 0.5, H24: 0.5
13.3.5.5
29
Short for "under consideration"