i
i
NOTE
If you change the Network type during ongoing operation, check settings, measured values, and limiting
values for inconsistencies. Check also the ICD/IID file which is suitable for the network type. If there are any
invalid measured values and limiting values or a wrong ICD file, restart the device.
Configuration via Display
Submenu Basic Parameters
[dw_p85x_submenu_basic_settings, 1, en_US]
Figure 2-14 Submenu, Basic Parameters
Table 2-10 Basic Parameter Settings
Parameter Default Setting Setting Range
Voltage Inputs
Connection type 3P4W 1P2W (1-phase system)
3P3WB (3-wire, equal load)
3P3W_2I (3-wire, any load (2*I))
3P3W_3I (3-wire, any load (3*I))
3P4WB (4-wire, equal load)
3P4W (4-wire, any load)
PT primary 400.0 V 1.0 V to 1 000 000.0 V
PT secondary 400.0 V 1.0 V to 600.0 V
2.5.2
Basic Functions
2.5 AC Measurement
48 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022