[sc_q100_communication ethernet, 3, en_US]
Figure 2-26 Configuration Tab, Ethernet Settings
Configure the respective parameters according to the following table.
Table 2-18
Settings for Communication Ethernet
Parameter Default Setting Setting Range
Communication Ethernet
IP address
4
192.168.0.55 Any
0.0.0.0 = DHCP
Subnet mask
4
255.255.255.0 Any
Default gateway
4
192.168.0.1 Any
Ethernet switch on No No
Yes
Enable SNMP No No
Yes
Bus protocol Modbus TCP -None-
Modbus TCP
IEC 61850
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to Table 2-3).
Click Activation.
Configuration via Display
Submenu Ethernet Settings
The operation is carried out with the softkeys F1 to F4.
2.6.1.3
4
After the parameter changes have been enabled, the device will restart.
Basic Functions
2.6 Ethernet Communication
64 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022