Parameter Default Setting Setting Range
Keep alive time 10 s 0 s = switch off
1 s to 65 535 s
Communication supervision
time
600 (* 100 ms) 0 s = none
100 ms to 6 553 400 ms
NOTE
The 2 port numbers must be different from each other.
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to Table 2-3).
•
Click Activation.
Number of Connections (not configurable)
Up to 5 TCP connections are possible:
•
Without user-defined port 1: 4 connections via the standard port 502
•
With user-defined port 1: 2 connections via the standard pot 502 and 2 connections via the configured
port number
Configuration via Display
Submenu Modbus TCP Settings
The operation is carried out with the softkeys F1 to F4.
[dw_p85x_display_communication_Modbus_TCP, 1, en_US]
Figure 2-29 Submenu Communication via Modbus TCP
Diagnosis of the Modbus TCP
The diagnosis for the Modbus TCP allows analyzing parameters and communication as well as resetting the
diagnostic counters.
NOTE
The diagnostic data of Modbus TCP are displayed only if the bus protocol has been selected in the tab
Configuration → Basic configuration → Communication Ethernet.
If the protocol has not been selected, the Diagnosis Modbus TCP window displays -none-.
For the diagnosis of the protocol Modbus TCP in the Maintenance tab, proceed as follows:
•
In the navigation window, click Modbus.
The Modbus window opens and the Modbus TCP protocol is displayed. For Modbus TCP the Standard
server, the User-port server and the Connection data are analyzed.
2.6.2.2
2.6.2.3
Basic Functions
2.6 Ethernet Communication
SICAM, SICAM P850/P855 7KG85X, Manual 67
E50417-H1040-C482-A9, Edition 03.2022