Configuration and Value View via Web Pages
Configuration of the Binary Outputs
To change the settings of the binary outputs in the Configuration tab, proceed as follows:
•
In the navigation window, click Binary outputs.
[sc_q100_BO_configuration, 2, en_US]
Figure 3-5 Configuration Tab, Binary Outputs
•
Configure the respective parameters according to the following table.
Table 3-1
Settings for Binary Outputs
Parameter Default Setting Setting Range
Source type Indication Indication
Energy counter
Source Type Indication
Indication
6
-none- Acc. to list box
Source inverted
(can be set individually for all
relay outputs)
No No
Yes
Operating mode
7
(can be set individually for all
relay outputs)
Persistent Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating
mode (setting only possible for
operating modes Pulse and
Pulse with retrigger)
20 (* 10 ms) 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter
6
-none- Acc. to list box
Energy increase per pulse 1.00 Wh 0.10 Wh/VAh/varh to
1 000 000.00 Wh/VAh/varh
Output time for pulse operating
mode
20 * 10 ms = 200 ms 50 ms to 3 600 000 ms
3.2.2
6
If you select -none- as the source of an indication or energy counter, the corresponding binary output is inactive.
7
If you have selected one of the 2 Pulse types in the Operating mode list box, enter an output time x (in x *10 ms) in the Output
time for pulse operating mode field.
Process Connections
3.2 Binary Outputs