[sc_q100_Limits_configuration, 2, en_US]
Figure 4-2 Configuration Tab, Limits (Example)
•
Configure the respective parameters according to the following table.
Table 4-1 Settings for Limits
Parameter Default Setting Setting Range
Measurement -none- Measured value selection list depending on
network type
Limit
0.00
8
-1 000 000 000.00 to 1 000 000 000.00 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.00 0.00 to 10.00
Violation indication Limit Violation x
(x = 1 to 16)
The name of the indication is customizable;
max. 31 characters.
•
After the parameterization, click Send.
•
In the navigation window, click Activation and cancel.
•
Enter the activation password (refer to Table 2-3).
•
Click Activation.
NOTE
Select -none- for Measurement to disable the corresponding limit indication.
It depends on the configured network type which quantities are offered in the list box of the Measure-
ment. The Network type is specified in the Basic configuration > AC measurement.
Value View of the Limits
To display the limits in the Value view tab, proceed as follows:
•
In the navigation window, click Limits.
8
The limit value must be the primary value.
Automation Functions
4.1 Limits
SICAM, SICAM P850/P855 7KG85X, Manual 93