Figure 4-6 Example: Linking 2 Indications to a Group Indication
Configuration and Value View via Web Pages
Configuration of the Group Indications
To change the settings of the group indication in the Configuration tab, proceed as follows:
In the navigation window, click Group indications 1-4.
[sc_Group_indication_configuration, 5, en_US]
Figure 4-7 Configuration Tab, Group Indications
Configure the respective parameters according to the following table.
Table 4-3
Settings for Group Indications
Parameter Default Setting Setting Range
Source
Only the indications for the
parameterization of the binary
outputs are displayed which
can be used according to the
current device settings.
-none- Acc. to list box
Limit violation and group indication:
Designation can be changed during the parame-
terization.
Source inverted No No
Yes
4.2.2
Automation Functions
4.2 Group Indications
96 SICAM, SICAM P850/P855 7KG85X, Manual