Engineering via SICAM WEB
SICAM RTUs, User Manual SICAM CMIC 191
DC8-001-2.09, Edition 08.2016
Processing type Parameter Meaning
latch_prompting Latch prompting can be different to the trans-
mission prompting (S)
Value range Value range of the counter (S)
Pulse value Pulse value (S)
0.0001 bis 9999
Moduleselection_SVM_
monitoring
Switch for power monitoring handling (PM)
Standard PM (PM inputs per modules) or input
IN D17 of one BI-module as PM input for all
modules Attention: Selected module must be
a DI-module.
SW_DI – software data
point digital input
SW_DI_AR - automatic
reclosing
SW_DI_UPDATE – up-
date of double-point in-
formation
Originatoraddress Allowed originator address
QOC there is no confirmation/termination for a re-
ceived command with a different QOC
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE Source identification supplementary system
element
SW_DI_BT – breaker
tripping
SW_DI_SOR – switching
operation running
SW_CV_SET – counter
set
SID-BSE Source identification basic system element
SID-ST Source identification station number if mul-
tipoint traffic mode 0…99 if R-SID 0…254. If
automatic then the source ID will be learned.
SID-SSE Source identification supplementary system
element