EasyManua.ls Logo

Siemens SICAM CMIC - Recovering Device Settings

Siemens SICAM CMIC
414 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering via SICAM WEB
264 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
5.3.3 Recovering Device Settings
This function gives you the possibility of restoring and loading all previously backed up set-
tings and parameterizations into the device.
With this procedure, all telecontrol parameters, instruction list and firmware codes are stored
jointly on the SD card in the master control element.
Select thereto the submenu Restore device settings .
You have the possibility to abort the procedure.
Click Select a file in order to open the selection dialog
Select the source directory and the source file (file type must be cmc)
Click on the button
The target device starts the loading procedure. The duration of the loading procedure de-
pends on the file size and the used communication connection.
Subsequently the file is checked upon integrity. Thereto, a cryptologic hash function is calcu-
lated over the file and the result is compared with the hash value in the filename:
If the file is valid, the data is written on the SD card of the target device and all settings in
the target device are adapted
With different results, the file is deleted and no changes are carried out; an error infor-
mation is displayed
After successful upload, the target device will be restarted:
Click on the button in order to close the dialog