Use Cases
396 SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
F.1 SICAM CMIC as Telecontrol Substation
Features:
• Communication with the control system via IEC 60870-104
• 1 IP address
• 1 subnet-mask
• 1 default router
• Communication to the process with local peripherals or serial communications protocols
(e.g.: MODBUS, …)
• Parameter Network settings | IP address | Mode of Ethernet ports = 1 IP
address (connected ports in switch mode)
In this configuration SICAM CMIC can be reached with the set IP address via both Ether-
net interfaces (X1 or X4). The unused port is not deactivated.
Substation Zone
Office Zone
Control Center Zone
SICAM CMIC
Process
IP-address: 172.17.0.22
PREx / ET84
IP-address: 172.16.0.3
Default router: 172.16.0.254
IP-address: 172.16.0.254