5.10 Updating the Firmware
118 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5.10 Updating the Firmware
Proceed as follows to update the firmware:
1. Establish a connection to the device. From the menu bar, select ConnectionSetup con-
nection and set the following parameters in the Setup device connection dialog:
Device connection: Serial connection
Device address: address 0 is valid for all devices
Interface: e.g. COM1
Baud rate: 9600 Baud at delivery
depends on adapter type RS485
Note
Make sure to set the same parameter values in SICAM P Parameterization and in the device. In
the device, the serial interface must be set to "PC-RS 485".