6
6.3 Procedure
130 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
6.3 Procedure
• First, connect the SICAM P as described in chapter 6.2.
• You can adjust the device manually or via programming software
Procedure at the device
• Select Basic settings → Connection / Transformer.
Select the range to be adjusted (e.g. AC 228 V).
• In the menu, select: Calibrate.
A dialog window appears.
• Enter the setpoint value for adjustment voltage and adjustment current. Default setpoints are
the nominal ranges of the measuring ranges set under Connection / Transformer. Optimal
precision can be achieved by using these default setpoint values. If the default values are not
available, make the appropriate changes.
• Switch the adjusting device on with the setpoints.
• Follow the instructions. SICAM P is readjusted.
Procedure for programming software
• Establish the communication between device and programming software.
• In the menu, select: Calibration
A dialog window appears.
• Select the element you wish to adjust: U or I
• Enter the setpoints for adjustment of voltage and current. The setpoints given are the nominal
values of the measurement ranges set under Connection / Transformer. These preset set-
points ensure optimum precision. If the preset values are not correct, change them accord-
ingly.
• Switch the adjusting device on with the setpoints.
• Follow the instructions. SICAM P is readjusted.
Calibration of the
selected input range.
Please follow the in-
structions in manual!
<ok
<cancel