1
1.4 Dimensions
18 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Fig. 1-3 SICAM P 7KG7750
Technical Data for Housing
Housing: Flush mounting according to IEC 61554/DIN 43700
Panel section: 92.0
+0,8
mm x 92.0
+0,8
mm
Protection class: front IP 41 or IP 65
terminals IP 20
for personal security IP 1x
Terminals
Terminals for power supply, voltage inputs, current inputs, binary outputs, I/O modules
(optional):
Conductor cross section, rigid max.: 2.5 mm
2
Conductor cross section with ferrule: 1.5 mm
2
Stripping length: 9 mm
Tightening torque: 0.4 Nm to 0.5 Nm
RS485 interface 9-pole D-Sub miniature female connector
Note: All dimensions in mm