4
4.4 Basic Settings
62 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Caution
• You must make these settings for a direct connection or for a connection with current trans-
formers.
• The selected measuring range must be greater than the secondary rating of the current
transformer!
• The accuracy of SICAM P (see table 3-3) is based on the selected measuring range.
• The determination of this range indicates the maximum current value that can be displayed
on the device.
Example
CT rating: 500 / 1 A
Measuring range 1.2 A: Maximum display range: AC 0 A to 600 A
Measuring range 6 A: Maximum display range: AC 0 A to 3000 A
4.4.2.2 Voltage Transformer
• Yes: Voltage transformers are utilized (max. primary: AC 1000 kV, secondary: AC 600 V)
• No: Voltage transformers are not utilized
Measuring range
• 132 V nominal input AC 100/110 V
• 228 V nominal input AC 190 V
• 480 V nominal input AC 400 V
• 828 V nominal input AC 690 V
Note
When you change the current transformer settings, the power calculation in the device has to be
reset.
*voltage transf.:No
kV/ V
*meas. range L-L 480V
<ok
<cancel