4.4 Basic Settings
64 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
4.4.3 Outputs
Here, the user can determine the function of the programmable output contacts (potential-free
electronic relays). Further contacts can be assigned in devices with I/O modules of the binary
output or relay output type (option).
Selection
Off Contact has no function
SICAM P is on Contact closed if power supply voltage is present.
Energy pulses If selected, a new window "Energy Pulses" appears.
Limit value 1 If selected, a new window "Limit Value 1" appears.
Limit value 2 If selected, a new window "Limit Value 2" appears.
Limit value 3 If selected, a new window "Limit Value 3" appears.
Limit value 4 If selected, a new window "Limit Value 4" appears.
Limit value 5 If selected, a new window "Limit Value 5" appears.
Limit value 6 If selected, a new window "Limit Value 6" appears.
Limit value 7 If selected, a new window "Limit Value 7" appears.
Direction of rotation This option allows you to output the rotation direction of the voltage.
1: Contact activated; direction of rotation for clockwise display
(phase sequence L1-L2-L3, clockwise rotation)
0: Contact deactivated; direction of rotation for anti-clockwise display
(2 phases interchanged, anti-clockwise rotation)
*relay1: limit value1
*relay2: rotation
<ok
<cancel