4
4.4 Basic Settings
72 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Uen
Measurement (default setting)
Calculation
Uen will be calculated if terminal N is grounded (standard application).
Uen has to be measured if L2 or L3 is grounded (special application).
Figure 4-1 Network connection with grounded phase L2
Analog output setting (only visible in screen for devices with optional analog output module)
If the device is equipped with an optional analog output module (see table 1-2, order code D),
analog outputs are configured in following screen:
These settings allow writing the transduced measured values (range 0 mA to 20 mA) to analog
outputs of analog output module via Modbus master or IE 60870-5-103 master.
Start value
holding
After power interruption the analog output is set to last in register saved value.
default
After power interruption the analog output is set to current value in register.
a
b
P1 P2
S1 S2
c
P1
S1 S2 S1 S2
P1
P2
P2
AAA
BBB
aaa
bbb
PE
resp.
10 A
Analog output setting
*start value:holding
*range from: -32767
* to: 32767
*current range:0-20mA
<ok
<cancel