4.8 Parameterization Screens
76 Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Illumination
0 min to 99 min
0 min = Illumination off
99 min = Illumination on permanently
Contrast
0 to 9 (default setting: 4)
Screen structure
The contents of specific measuring screens are programmed on the "Screen Structure" window.
Screen
Selection of a specific screen among the number previously established. The contents of the
screen are automatically displayed when switching from one screen to the next.
Contents
The contents of the selected screen can be established or modified here as follows:
3 measured values digital
6 measured values digital
3 Min - Max values
Voltages, currents, cos φ, phases L1, L2, L3
If specific screen content is selected, the input fields for the corresponding characteristics are
automatically displayed.
*screen no.: 10
*type: min-max
*1:Ua
*2:Ub
*3:Uc
<ok
<cancel