5
5.7 Input / Output Modules
99Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
5.7.6 Binary Inputs (optional)
The binary inputs (optional) can be used for static messages and impulse inputs.
Proceed as follows:
1. Activate/Deactivate one or both binary inputs by ticking the corresponding check box under
1. and/or 2.
2. For each input used, set the Designation together with the Dimension.
3. If you want to use the input as an external counter, you have to define the Factor e.g. as
Energy increase per pulse (refer to chapter 5.7.2).
4. If you want to use the binary input to display binary information (0/1), 0 must be entered as
a factor.
5. Choose the binary input to be used for time Synchronization via minute impulses. The
device will display the designation, not the number of the Binary input.
6. Analog to measured values, binary inputs may be displayed on measurement screens (see
chapter 5.6.2).
Note
The designation of the binary input is displayed instead of the binary input number!