Parameters and Properties
18
Power Meter, IEC 60870-5-103, Manual
E50417-B1076-C375-A4, Release 11.2012
2.2.2 Standard ASDUs in Monitoring Direction
Table 2-2 Standard ASDUs in monitoring direction
# Designation
Supported by
SICAM P
7KG7750/55?
Remark
ASDU 1 Time-tagged message yes
All available events and binary informa-
tion with time stamp. Also the information
from modules in additional module slot.
ASDU 2 Time-tagged message with relative time no -
ASDU 3 Measurands I no -
ASDU 4 Time-tagged measurands with relative time no -
ASDU 5 Identification yes
Function type: 130
Manufacturer (eight ASCII characters):
„SIEMENS“
SW identification (four ASCII characters):
e.g. „0400“ = Version V04.00
ASDU 6 Time synchronization yes -
ASDU 8 General interrogation termination yes -
ASDU 9 Measurands II yes
refer to chapter 3.1.2,
“Measured Value Telegrams”
ASDU 10 Generic data yes see chapter 3.1.2.10
ASDU 11 Generic identification no -
ASDU 23 List of disturbance data no -
ASDU 26 Ready for transmission of disturbance data no -
ASDU 27 Ready for transmission of channel no -
ASDU 28 Ready for transmission of tags no -
ASDU 29 Transmission of tags no -
ASDU 30 Transmission of disturbance values no -
ASDU 31 End of transmission no -