Data Mapping
22
Power Meter, IEC 60870-5-103, Manual
E50417-B1076-C375-A4, Release 11.2012
3.1 Measured Quantities
3.1.1 Mapping
3.1.1.1 Measured Values Mapping
The SICAM P 7KG7750/55 device supports transmission of measured values via the
communication protocol IEC 60870-5-103.
All measured values are transferred as per-unit values.
The column "100 % corresponds to" in the table below shows the relation between the
100 % per-unit value and the corresponding measured value. Additional explanations
are given below the table.
Please also refer to chapter 2.1.2 for the selection of the measured value ranges via
protocol.
# Value Measured quantity
100 %
corresponds to
Function
type
Information
number
Compatibility
Data unit
Position
1 Van Voltage (A-N) V
L-N (nom.)
130 148 yes 9 4
2 Vbn Voltage (B-N) V
L-N (nom.)
130 148 yes 9 5
3 Vcn Voltage (C-N) V
L-N (nom.)
130 148 yes 9 6
4 Vab Voltage (A-B) V
L-L (nom.)
130 151 no 9 1
5 Vbc Voltage (B-C) V
L-L (nom.)
130 151 no 9 2
6 Vca Voltage (C-A) V
L-L (nom.)
130 151 no 9 3
7 V Average Voltage V
L-N (nom.)
130 151 no 9 4
8 Ia Current (A) I
(nom.)
130 148 yes 9 1
9 Ib Current (B) I
(nom.)
130 148 yes 9 2
10 Ic Current (C) I
(nom.)
130 148 yes 9 3
11 I Average Current I
(nom.)
130 151 no 9 9
12 3I0 Neutral Current I
(nom.)
130 151 no 9 10
13 Pa Real Power (A) I
(nom.)
* V
L-N (nom.)
130 150 no 9 1
14 Pb Real Power (B) I
(nom.)
* V
L-N (nom.)
130 152 no 9 1
15 Pc Real Power (C) I
(nom.)
* V
L-N (nom.)
130 152 no 9 2
16 P Real Power 3 * I
(nom.)
* V
L-N (nom.)
130 148 yes 9 7
17 Qa Reactive Power (A) I
(nom.)
* V
L-N (nom.)
130 150 no 9 2