Communication
6.2.4 Information mapping table
SICAM P35 P36, 3-phase Multi-Function Power Meter, User Manual
E50417-H8940-C562-4, Release Date 06.2018
43
Alarm manner
control byte
0103 H unsigned int 2 bytes R/W 0...3
0: turn off alarm function
1: relay output 1 is used
for alarm
2: relay output 2 is used
for alarm
3: output ports 1 and 2
are all used for alarm
Alarm status byte 0106 H unsigned int 2 bytes R 0...0x3F
From low to high, each
bit means status of an
alarm group:
0: no alarm activated
1: in alarm status
BO1 Relay oper-
ation time
0107 H unsigned int 2 bytes R/W
0 or
100...3000
Unit: ms. Value 0 is for
latched output; value
100~3000 for pulse
output
BO2 Relay oper-
ation time
0109 H unsigned int 2 bytes R/W
0 or
100...3000
Unit: ms. Value 0 is for
latched output; value
100~3000 for pulse
output
Alarm 1
Limit viola-
tion data type
0110 H unsigned int 2 bytes R/W 0...31 See alarm type table
High 16 bits
of limit viola-
tion threshold
0111 H
unsigned long 4 bytes R/W
Arbitrary
value
Threshold=set val-
ue/100
Low 16 bits
of limit viola-
tion threshold
0112 H
Limit viola-
tion detection
type
0113 H unsigned int 2 bytes R/W 0...1 0: over, 1: below
Alarm port 0114 H unsigned int 2 bytes R/W 0...3
0: off
1: alarm output to relay
output 1
2: alarm output to relay
output 2
3: alarm output to output
ports 1 and 2
Alarm 2
0115 H
...0119 H
10 bytes R/W See Alarm 1
Alarm 3
011A H
...011E H
10 bytes R/W See Alarm 1
Alarm 4
011F H
...0123 H
10 bytes R/W See Alarm 1
Alarm 5
0124 H
...0128 H
10 bytes R/W See Alarm 1
Alarm 6
0129 H
...012D H
10 bytes R/W See Alarm 1
Parameter Address Data Type Length R/W
Data
Range
Remark